Load Break Switch NXS700004

Load Break Switch NXS700004

  • Opening and closing under severe weather conditions, and easy installation on poles thanks to its high level of integration (MV transformer embedded in the SF6 chamber)
  • Two equipment in one, a load break switch and a disconnector
  • Rescue manual command by a telescopic adjustable linkage or by a 3 positions hook stick command
  • Maintenance free
  • Consult us to define your needs (options, packaging, etc.)
Code NXS700004
GTIN 03700540438086
Name Load Break Switch
Load Break Switch
Contact sales

Technical information

Technical specifications

Dimensions
Weight 140 kg
Height 512 mm
Width 1489 mm
Length 1396 mm
Standards
Standards IEC 62271-1, IEC 62271-103, IEC 62271-102, IEC 62271-200, IEC 60265
Electrical values
Rated Voltage (Ur) 24 kV
Rated current 630 A
Rated line charging breaking current 40 A
Rated cable charging breaking current 40 A
Lightning impulse withstand level of voltage (1.2/50) 125 kV
Rated frequency 50-60Hz
Mainly active load breaking 630 A
Rated close-loop breaking current 630 A
Rated short-circuit making current 12.5 kA
Rated short-time withstand current (1s) 20 kA/s
Rated short-time withstand current (peak) 31.5 kA/s
Rated no-load transformer breaking current 25 A
50 kV
Features
Mechnanical endurance 5000 C/O cycles M2 Class
Electrical endurance 300 >E3 Class
Degree of protection IP66/IP68
Creepage distance 900 mm
Pollution degree 4
Altitude/above sea level 1000 m
Operation under ice 20 mm
Temperatures
Operating temperature -50 ... 50 °C
Storage temperature -50 ... 50 °C
Relative humidity at 40°C 98 %

Packaging

Pallet package
Size 1 pce
Weight 145.000 kg