| Dimensions |
| Weight |
150 kg |
| Height |
470 mm |
| Width |
1500 mm |
| Length |
1100 mm |
| Standards |
| Standards |
IEC 62271-103, IEC 62271-102, IEC 62271-1, IEC 62271-200, IEC 60265 |
| Electrical values |
| Rated voltage (Ur) |
24 kV |
| Rated current |
400 A |
| Rated line charging breaking current |
40 A |
| Rated cable charging breaking current |
40 A |
| Lightning impulse withstand level of voltage (1.2/50) |
125 kV |
| Rated frequency |
50-60Hz |
| Mainly active load breaking |
400 A |
| Rated close-loop breaking current |
400 A |
| Rated short-circuit making current |
12.5 kA |
| Rated short-time withstand current (1s) |
20 kA/s |
| Rated short-time withstand current (peak) |
50 kA/s |
| Rated no-load transformer breaking current |
25 A |
|
50 kV |
| Features |
| Mechnanical endurance |
5000 O/C operation cycles Class M2 |
| Electrical endurance |
300 C/0 operation cycles Class E3 |
| Degree of protection |
IP66/IP68 |
| Creepage distance |
960 mm |
| Pollution degree |
4 |
| Altitude/above sea level |
1000 m |
| Operation under ice |
20 mm |
| Option 1 |
- Additional linkage tubes for 14-16m height poles,- Manually operated with a hook stick,- Operations counter,- SF6 pressure manometer,- Surge arresters,- Animal protections for live parts,- Customized position indicators (O/I black/white, ON/OFF green/red, O/I greeen/red),- Equipotential platform (Folding, Fixed, Adjustable,- Fixation on poles (Clamping, Strapping, Bolting) |
| Option 2 |
- Commande manuelle par perche,- Compteur de manœuvres,- Fixation sur poteau par bridage, cerclage, vissage,- Indicateur de position personnalisé (O/I noir et blanc, ON/OFF vert/rouge, O/I vert/rouge),- Manomètre de pression SF6,- Parafoudres,- Plateforme d'équipotentialité (Repliable, Fixe, Orientable,- Protection avifaune,- Supplément tringlerie pour utilisation sur poteaux de 14 à 16m |
| Temperatures |
| Operating temperature |
-50 ... 50 °C |
| Storage temperature |
-50 ... 50 °C |
| Relative humidity at 40°C |
98 % |