CC vertical crossarm SH181

CC vertical crossarm SH181

For suspending double, three phase covered conductor lines. Set includes three 2 phase horizontal cross-arms which will be installed vertically to the same pole. Allowed loads for the crossarm at conductor fixing points are: Fx= 3.0 kN angle load, Fz= 3.6 kN horizontally along conductor, Fy= 3.5 vertically downwards. To fulfil the minimum distance requirement between conductor and brace 220 mm, the minimum distance is 730 mm.

Code SH181
GTIN 6418677406973
Name CC vertical crossarm
20 kV, double line
Contact sales

Technical information

Technical specifications

Dimensions
Weight 33 kg
Features
Insulator pin OT24
Mechanical
Allowed loads at conductor fixing point Fx = 3.0 kN, Fz = 3.6 kN, Fy = 3.5 kN
ETIM
ETIM Class EC003515
Type Support cross arm
Suitable for One pole
Profile shape RHS (Rectangular Hollow Section)
Material Steel
Surface protection Galvanized
Conductor surface Covered
Max. rated voltage 20 kV

Packaging

Carton
Size 1 pcs
Weight 33.050 kg
Pallet package
Size 10 pcs
Depth 1200 mm
Width 800 mm
Weight 350.500 kg