Circuit breaker NX2003253

Circuit breaker NX2003253

The protection and management of MV / LV transformers in rural areas require the use of specific Circuit Breakers adapted to significant load imbalances and thus guarantee the total use of the installed power even in unbalanced conditions. These devices (4 poles - 3 protected) use air-break technology with chambers with metal partitions to cut the arc.

Code NX2003253
GTIN 03700540411119
Name Circuit breaker
Pole Mounted Circuit Breaker D265T (Middle Pole) with Digital Trip Unit
Contact sales

Technical information

Technical specifications

Dimensions
Weight 19 kg
Height 550 mm
Width 370 mm
Length 400 mm
Standards
Standards HN 63-S-11
Electrical values
Rated Voltage (Ur) 0.44 kV
Rated current 265 A
Rated short-circuit breaking capacity 6.4 kA
Rated short-circuit making current 11.7 kA
Rated short-time withstand current (1s) 6.4 kA/s
10 kV
Lightning impulse withstand level of voltage (1.2/50) 20 kV
Features
Degree of protection IP31
Output number 2
Conductor size 50 - 150mm²
Temperatures
Operating temperature -25 ... 50 °C
Storage temperature -25 ... 70 °C

Packaging

Carton
Size 1 pce
Weight 19.050 kg
Pallet package
Size 24 pcs
Weight 462.200 kg