Surge Arrester NX7230830

Surge Arrester NX7230830

Protection of transformers, switchgears and transmission lines against atmospheric and switching overvoltages. Selection of arrester has to be carried out according to IEC 60099-4.

Code NX7230830
GTIN 03700540438482
Name Surge Arrester
Uc=12kV, In=10kA, Class DH
Contact sales

Technical information

Technical specifications

Dimensions
Weight 1.6 kg
Length 320 mm
Temperatures
Ambient temperature -35...+35ºC
Features
Site pollution severity class e (IV)
Long duration current impulse withstand 300 A
Max lightning residual voltage at 10 kA 40 kV
Max steep current residual voltage at 10 kA 42 kV
Max switching residual voltage at 500 A 31 kV
Rated short circuit current (Is) 20 kA
Specified long-term load (SLL) 200 Nm
Specified short-term load (SSL) 250 Nm
Thermal charge transfer rating (Qth) 1.1 C
Wet power frequency withstand voltage of the housing 45 kV
Rated Voltage (Ur) 15 kV
Creepage distance 650 mm
Continuous operating voltage (Uc) 12 kV
Nominal discharge current (In) 10 kA
Arrester Classification-Designation DH
Line discharge class 1
Repetitive charge transfer rating (Qrs) 0.5 C
High current impulse withstand 100 kA
Dry lightning impulse withstand voltage of the housing 110 kV
ETIM
ETIM Class EC002676
Continuous voltage AC 12 kV
Rated voltage AC 15 kV
Creepage path 650 mm
Height 320 mm
Application Exterior area

Packaging

Carton
Size 1 pce
Weight 1.650 kg