ITI 2012-1S manages in Local or Remote mode from a scada, one substation MV swithgear.
| Code | NX2009603 |
| GTIN | |
| Name | Grid Automation Controller Control box ITI 2012-1S |
Grid Automation Controller NX2009603
ITI 2012-1S manages in Local or Remote mode from a scada, one substation MV swithgear.
| Code | NX2009603 |
| GTIN | |
| Name | Grid Automation Controller Control box ITI 2012-1S |
| Dimensions | |
|---|---|
| Weight | 38 kg |
| Height | 650 mm |
| Width | 330 mm |
| Length | 310 mm |
| Standards | |
| Standards | HN 64-S-44 |
| Electrical values | |
| Rated voltage (Ur) | 0.23 kV |
| Rated insulation voltage max | 2kV 50Hz 1min 10kV 50Hz 1min on BT Input; 20kV 1.2/50µs inpluse |
| Rated impulse withstand voltage | 5 kV |
| Features | |
| Communication protocols | IEC 60870-5-101, IEC 60870-5-104, DNP3 serial, MODBUS RTU, HNZ |
| Communication media | Digital radio, GSM/GPRS, xG router, optic fiber, PSTN |
| Protection relay | Definite time earth fault and definite time overcurrent fault detection Directionnal Earth fault and overcurrent fault detection |
| Degree of protection | IP2XC |
| Automation | Auto sectionalizing Function (ASF) Automatic Switching of Power Sources (ASPS) |
| Measurements | Network load current on each phase MV voltage measured through the MV/LV voltage transformer 1000 time stamped events |
| Sensors | - 3 openable Toroidal Current sensors ratio 500/1 - 3 voltage sensor used for Directionnal fault detection |
| Configuration | With a laptop equipped with a browser |
| Installation | Installation on a wall of substations |
| Carton | |
|---|---|
| Size | 1 pce |
| Weight | 38.050 kg |