IPC / Bare connector SLW34.6

IPC / Bare connector SLW34.6

The connector can be used for medium voltage covered conductor to bare conductor connections. Nominal insulation thickness of the conductor can be between 2.3-4.0 mm.

Code SLW34.6
GTIN 6438100356620
Name IPC / Bare connector
50-241 mm² / 35-157 mm²
Contact sales

Technical information

Technical specifications

Certificates
Standards EN 50397-2:2009
Dimensions
Weight 0.286 kg
Main conductor mm² 35-157 mm² AlMgSi
Branch conductor mm² 50-241 mm² AlMgSi
Cable diameter 14.2 - 26.1 mm
Conductor diameter 6.8 ... 16 mm
Mechanical
Tightening torque Nm 35 Nm
ETIM
ETIM Class EC001062
Material main conductor Aluminium
Material branch conductor Aluminium
Clamping channel opening main conductor Both sides open
Clamping channel opening branch conductor Both sides open
Surface protection Bare
Type of connection Insulation piercing connector IPC

Packaging

Carton
Size 24 pcs
Depth 305 mm
Height 205 mm
Width 255 mm
Weight 7.364 kg
Volume 15.943875 l
Pallet package
Size 864 pcs
Depth 1200 mm
Height 970 mm
Width 800 mm
Weight 285.104 kg
Volume 931.2 l