Distribution Panelboard NX2004071

Distribution Panelboard NX2004071

TUR panelboards protect and dispatch LV distribution network in MV / LV substations, just behind the 400 kVA transformer TUR panelboards include a LV tetrapolar Load Break Switch with visible break, interchangeable 400A Outgoing Feeders with distributed neutral, these feeders are equipped with 3 fuses (operable under voltage) and a rotary link to disconnect the Neutral.

Code NX2004071
GTIN 03700540417791
Name Distribution Panelboard
LV TR4-800I panelboard with ACG wiring
Contact sales

Technical information

Technical specifications

Dimensions
Weight 32 kg
Height 1450 mm
Width 630 mm
Length 480 mm
Standards
Standards HN 63-S-61 (1979)
Electrical values
Rated Voltage (Ur) 0.44 kV
Rated current 800 A
Rated mainly active load-breaking current 800 A
Rated short-time withstand current (peak) 32 kA/s
Rated short-time withstand current (0,5s) 16 kA/s
Rated short-circuit making current 16 kA
10 kV
Lightning impulse withstand level of voltage (1.2/50) 20 kV
Features
Feeders max numbers 4
Temperatures
Operating temperature -5 ... 40 °C
Storage temperature -25 ... 70 °C

Packaging

Pallet package
Size 1 pce
Depth 1200 mm
Width 800 mm
Weight 52.000 kg